L4 fire alarm system requirements: detection in the escape routes only

L4 puts automatic detection in the escape routes and nowhere else. Not the rooms opening onto them, not the high risk areas, just the corridors, lobbies and stairs people will use to get out. It is a small category with a narrow proper use, and it turns up more often as the result of a system being cut back than as the result of a design decision.

The one thing L4 is protecting

The purpose is to detect smoke in the escape route itself, so that people are warned before the route becomes unusable. It assumes that a fire starting in a room will be noticed by an occupant and raised at a call point, and that the escape route detection is the backstop for smoke spreading into the corridor. Everything about the category follows from that single assumption.

Where the assumption holds

It holds in a building that is genuinely occupied throughout, where rooms are small and visible, where doors onto the route are held closed and where nobody sleeps. Take any one of those away and the category is working on a premise that is no longer true. That is why L4 is rare in current designs and common in older installations that were adequate for a previous use.

L4 against L3

The difference is the rooms that open onto the escape route. L3 detects a fire in those rooms while the door is still shut; L4 waits until smoke reaches the corridor, which in a compartmented building can be a long time after the fire started and a short time before the route is lost. The cost difference is modest compared with the difference in warning time.

If a survey says you have L4

Check whether that was the design or the residue. Refurbishments remove detectors, partitions create rooms nobody assessed, and a system certificated as L3 fifteen years ago can survey as L4 today. Either way, the fire risk assessment is the place the current category has to be justified, and the certificate needs to match the building as it stands.

Questions people ask about l4 fire alarm system

Is an L4 system ever appropriate?

It can be, in a simple, fully occupied, non sleeping premises with good compartmentation. It should be an argued conclusion of the risk assessment rather than what was left after somebody saved money.

How do I know whether I have L3 or L4?

Look at the rooms that open onto your escape route. If they have detectors, it is at least L3 for that part of the building. A maintenance visit can survey and confirm the category actually installed.

Can L4 be upgraded to L3?

Usually yes by adding detection to the rooms opening onto the route, but it changes loop loading and cause and effect, so it is a design change with a new commissioning certificate rather than a fitting job.

Sources

Related answers

Get asbestos quotesSearch the register